Equipment testing under DGUV Regulation 3

šŸ”Š Listen to this article

An audio recording is not yet available for this article.

Practical overview for recurring tests of portable electrical equipment under DIN EN 50699 (VDE 0702).

DGUV DGUV A3 VDE 0702 Equipment testing Protection class RPE Protective conductor Schuko

Scope

This page is a field-oriented reference for recurring tests. The binding basis remains the current original standard, the operator risk assessment and the judgement of a qualified person.

DGUV A3 is a common field shorthand for equipment testing under DGUV Regulation 3; the canonical reference remains DGUV Vorschrift 3.

DIN EN 50699 (VDE 0702):2021-06 covers recurring tests. Tests after repair are handled separately by DIN EN 50678 (VDE 0701).

Inspection matrix

Device/protection classVisual inspectionProtective conductor RPEInsulation RISOLeakage/protective conductor currentTouch currentFunction
Class I - Schuko, metal enclosure āœ“ ≤ 0,3 Ī©* ≄ 1 MĪ© ≤ 3,5 mA ≤ 0.5 mA at accessible conductive parts without PE, where applicable āœ“
Class II - double insulated āœ“ - ≄ 2 MĪ© - ≤ 0,5 mA āœ“
Class III - safety extra-low voltage āœ“ - ≄ 0,25 MĪ© - - āœ“
Schuko extension lead / power strip āœ“ ≤ 0,3 Ī©* ≄ 1 MĪ© according to the applicable test method - Continuity / conductor assignment
Class I power supply with extra-low voltage output āœ“ ≤ 0,3 Ī©* depends on construction; separation/insulation according to the applicable test procedure ≤ 3.5 mA, where applicable ≤ 0.5 mA, where applicable āœ“
Class II power supply with extra-low voltage output āœ“ - depends on construction; separation/insulation according to the applicable test procedure - ≤ 0.5 mA, where applicable āœ“
* Note on RPE: The 0.3 ohm value is the usual practice reference for short protective conductor paths. Longer cables and specific constructions require the length allowance and assessment from the applicable current source.

SK I

Visual inspection, protective conductor continuity, insulation or substitute leakage method where required, leakage current assessment and functional test.

SK II / SK III

For double-insulated or SELV equipment the focus shifts to visual integrity, insulation barriers, touch current where applicable and function.

Extensions

Check connector condition, strain relief, conductor assignment, protective conductor continuity and insulation before field use.

Documentation

Record device ID, date, inspector, measuring device, measured values, result and next interval. Labels alone are not complete documentation.